We are getting message "PLC is Still in NOCONF, the downloaded application isn't a valid application" during program download to M580 CPU through Service port.
Article available in these languages:Japanese
This message usually come due to installation of CPU on wrong slot or CPU rack address is not set to 0 in case of rack expander module installed on the rack.