Simply connect the PC to the STBNIP2212 via Ethernet and launch the executable. Upon launching, it will prompt for the IP address. After entering the IP address, press enter, and it will automatically load the necessary file into the module. It's crucial to ensure that the STBNIP2212 module does not lose power during the firmware upgrade.
We have also included the steps captured during the firmware upgrade for your reference.
Please note that firmware upgrade is not possible in a running system, and during the upgrade, all configurations, applications, and initial values will be reset. Once the firmware upgrade is complete, the IP address of the NIM will revert to the default (MAC address) and will need to be reassigned. Additionally, the configuration will need to be downloaded again.
Refer attached document for more details.
Note: Firmware files can be downloaded from our website else you can also reach out to your country Customer Care team.