What is 'FBES' error in ATV320 Drive.
FBES is ATV logic FB Stop Fault

Probable cause :

When power is removed and drive stops, ATV320 shows FBES error that means 'Function blocks have been stopped while motor was running'
This is due to FBSN([Stop FB Stop motor])  is set to 'Freewheel'.
ATV320
If start/stop FB (function block) is by LI1, So at (LI1=Off) that FB is stopped while motor still running.

The error/fault can be disabled by going to 'Conf' press 'enter'  then set FBSN([Stop FB Stop motor]) to 'Ignore'. At Ignore state the drive does not stop.