How can we help you today?

How to configure Xenta Server (Xenta 511, 527, 555, 701, 711, 721, 731, 913) for automatic login.

Some customers may specify that the login screen to a Xenta Server be bypassed. The steps are described below:

1. Configure the user you want to automatically log in to the Xenta Server

2. Generate a certificate to avoid having the certificate error pop up every time you connect to the Xenta Server, go to XBuilder, and generate a certificate that has the same name as the IP address of the Xenta Server.

3. Edit Slogin.html and loggedout.html
- Connect to the Xenta Server using FTP
ftp://XXX.XXX.XXX.XXX
- The Slogin.html and loggedout.html are located in the folder www/index
Copy the files to your local hard drive
- Edit the files with, for instance, notepad and change the following
Slogin.html
Line 54
document.AuthForm.UserID.focus();"
document.AuthForm.UserID.focus(); send(AuthForm);"
Line 98
input type="text" name="UserID" value="" size="20" >
input type="text" name="UserID" value="user" size="20" >
Line 104
input type="password" name="PassWord" value="" size="20">
input type="password" name="PassWord" value="password" size="20">
loggedout.html
Line 5 (extra line, add < symbol at beginning of line)
meta http-equiv="refresh" content="2;url=/www/index/Slogin.html">

4. Carry out the changes
- Reconnect to the Xenta Server using FTP
- Change the names of the files that are already in the Xenta Server (Backup)
- Copy the files that from your hard drive to the Xenta Server

Schneider Electric India

Explore more

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more

Explore more

Need help?

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Start your sales enquiry online and an expert will connect with you.

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Centre

Find support resources for all your needs, in one place.