{}

Our Brands

Impact-Company-Logo-English Black-01-177x54

Welcome to the Schneider Electric Website

Welcome to our website.
How can we help you today?
Why F015 fault occurs in ATV310 Drive

Article available in these languages: Spanish

Name of fault :-
3 Output phases loss

Possible causes:-
• Motor not connected
• Motor power too low, below 6% of the rated drive current
• Output contactor open
• Transient instability in the motor current

Remedy:-
• Check the connections from the drive to the motor.
• Test on a low power motor or without a motor.
In factory settings mode, motor phase loss detection is active Output Phase loss detection  i.e 605 = 01.
To check the drive in a test or maintenance environment, without having to use a motor with the same rating , motor phase loss detection or Output Phase loss detection needs to be deactivated  i.e 605 = 00 & again set it to 1 when connecting back the motor.
• Check and optimize IR compensation in parameter 310, Rated motor voltage in parameter 304 and Rated motor voltage in parameter 305 and then perform Auto-tuning by setting parameter 318.

Schneider Electric India

Explore more
Range:
Articles that might be helpful Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Range: