Stop the Reporting Agent service on the Reports Server.
-
In WorkStation, in the System Tree pane, select the EcoStruxure BMS server that you want to restore.
-
On the Actions menu, click Restore .
-
In the Restore Options dialog box, in the Available restore points list, select a backup set in black text, which indicates that the backup set is compatible with the current version of the EcoStruxure BMS server.
-
Select the type of data you want to restore:
-
Select Configuration only to restore only configuration and custom object types' data.
-
Select All data to restore the configuration, historical, and custom object types data.
-
-
Click Restore .
-
Click Yes and Close .