How can we help you today?

what is the Hybrid output’s constant current flow in V257 and V259

Through the digital input there is constant current flow of about 2 mA. This can cause unwanted
operation of the semiconductor driven circuit breakers.

The semiconductor driven circuit breaker has a high resistance input resulting that the 2mA current
is enough to switch/activate the breaker unnecessarily.