Video: Clearing unit run hour violations on an Chilled Water Uniflair

Issue:
How to clear Unit Run Hours Violation on Uniflair Chilled Water cooling systems.

Product line:
Uniflair: TDCV700X, TDCV1000X, TDCV1200X, TDCV1700X, TDCV2500X, TDCV3400X, TDCV4000X, TDCV4300X, TUCV700X, TUCV1000X, TUCV1200X, TUCV1700X, TUCV2500X, TUCV3400X, TUCV4000X, TUCV4300X, HDCV4500X, HDCV5000X

Environment:
All Serial Numbers

Cause:
Install, Repair

Resolution

Press PRG

Use the DOWN arrow to scroll to Hourmeter Settings

Press ENTER

Use the DOWN arrow to scroll to Unit Run Hours

Press ENTER twice.

Press the DOWN arrow once

Press ENTER again to clear run hours.

Press ESC three times to exit back to main menu