What are the address details of Time Synchronization over IEC-103 protocol in MiCOM P225/P220
On P225/220 time synchronization over IEC 103, Please use the below address to write the time from your master. Date format setting (IEC / Private) will not affect time synchronization over IEC 103.
ASDU TYPE 6
COT 8
FUN 255
INF 0
Refer to the attachment for Address details & traces.
ASDU TYPE 6
COT 8
FUN 255
INF 0
Refer to the attachment for Address details & traces.