How to convert M580 BMENOC0301 / 311 version .2 to version .3

Prerequisites:

1. Unity Pro V11.1 must be installed on the PC and must include the Hotfix named “UnityPro_V111_HF0351921R App. Update - NOC .2 to NOC .3”.
or
Unity Pro V12.0 (or newer) must be installed on the PC

Conversion Steps:

1. Go to the following path:

%public%\Documents\Schneider Electric\Unity Pro\Extras\M580 Application Update

2. Launch the file M580ApplicationUpdate.exe.
3. Click on “Choose file” to select your application (the application must be a ZEF file).
4. Click on the “Next” button
5. The next screen will sum-up and check information needed for the conversion:
a. Application (PLC part number and version)
b. Unity Pro: not needed to update the application
c. DTM Library: not needed to update the application
If everything is correct, click on the “Next” button. If not, fix the error(s) found first.
Once the conversion has started, the process is on-going and may take a few minutes to finish.
6. After the conversion, the link to the converted application will be displayed with the possibility to open directly the directory containing the document.
Note: the converted application will be stored at the same location than the original application. The name will be suffixed by _converted.

Schneider Electric India

Explore more

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more

Explore more

Need help?

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Start your sales enquiry online and an expert will connect with you.

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Centre

Find support resources for all your needs, in one place.