How can we configure ground fault parameter in Tesys T
The LTM R controller measures ground currents and provides values in Amperes and as a percentage of
FLCmin.
The internal ground current (IgrΣ) is calculated by the LTM R controller from the 3 line currents
measured by the load current transformers. It reports 0 when the current falls below 10 % of FLCmin.
The external ground current (Igr) is measured by the external ground current transformer connected to
Z1 and Z2 terminals.
For configurable parameter check below attachment.
FLCmin.
The internal ground current (IgrΣ) is calculated by the LTM R controller from the 3 line currents
measured by the load current transformers. It reports 0 when the current falls below 10 % of FLCmin.
The external ground current (Igr) is measured by the external ground current transformer connected to
Z1 and Z2 terminals.
For configurable parameter check below attachment.