Is that possible to remote/automatic reset the electrical fault (SDE) in case of NSX MCCB?

The voluntary tripping by MN or MX or by"Push to trip" button , device reset can be automatic, remote or manual depending on the electrical diagram used with the SDE contact.
But the tripping due to an electrical fault (SDE) reset must be carried out manually (locally), this is for safety reason.  Means that after an electrical fault (trip unit or Vigi),
the customer have to reset manually by charging the handle. After the action of charging manually, the charge indicator changes to charged and the internal mechanism goes from the
Tripped position to the O (OFF). position,

Schneider Electric India

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:

Need help?

Need help?

Product Selector

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Get a Quote

Start your sales enquiry online and an expert will connect with you.

Where to buy?

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Centre

Help Centre

Find support resources for all your needs, in one place.

  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Centre
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Contact support - +1800-103-0011
  • Price List
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings