Why does an HMI read the wrong Modbus objects when using Function Code 04 with a Modicon M580 CPU?
Issue
An HMI using Modbus Function Code 04 (FC04) may read %I / %IW objects instead of the expected %M / %MW objects from a Modicon M580 CPU.
This can occur after migrating an application from a Premium PLC or when changing the Modicon M580 CPU configuration.
Product Line
- Modicon M580
- EcoStruxure Control Expert
Environment
The issue has been identified in configurations using:
- BMEP58xx20 CPU
- CPU firmware OS 3.0 or OS 3.1
- EcoStruxure Control Expert V15.0
Resolution
The behavior depends on the number of configured %I and %IW objects.
When the number of configured %I and %IW objects is 0, Modbus FC04 accesses the %M / %MW area.
When %I or %IW objects are configured, Modbus FC04 accesses the %I / %IW area.
With a BMEP58xx20 CPU using OS 3.0 or OS 3.1 in EcoStruxure Control Expert V15.0, the minimum number of %I and %IW objects cannot be configured to 0. As a result, an HMI using FC04 may receive %I / %IW objects instead of the expected %M / %MW objects.
The case information states that this behavior is planned to be addressed in EcoStruxure Control Expert V15.1.
Applicable Conditions
This FAQ applies when all of the following conditions are met:
- The HMI communicates with a Modicon M580 CPU using Modbus.
- The HMI uses Function Code 04 to access objects expected to be %M or %MW.
- The CPU configuration contains %I or %IW objects.
- The application depends on the legacy addressing behavior used with Premium CPUs.