{}

Our Brands

Impact-Company-Logo-English Black-01-177x54

Welcome to the Schneider Electric Website

Welcome to our website.
How can we help you today?
How to Read Smartlink Embedded Configuration Registers
Issue:
I got a "Slave Device Failure" Modbus exception when I read the Embedded Configuration Registers for a Smartlink device.

Resolution:
Embedded Configuration Registers for a Smartlink must by read with a block of 64 Registers

Example:
  • for Channel_1 - Input 1 => you need to poll 64 registers from Register 20010
  • for Channel_1 - Input 2 => you need to poll 64 registers from Register 20074
  • for Channel_7 - Input 2 => you need to poll 64 registers from Register 20778

Schneider Electric India

Explore more
Product:
Articles that might be helpful Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Product: