Under main menu,
ACC and DEC will be the first set of ramp up and down times.
Set AU1 to 0 to disable auto ramp feature.
Under AUF, F---:
Set F500 (acc2) for second ramp up time based on frequency threshold (F505).
Set F501 (Dec2) for second ramp down time.
Ramp switching can also be accomplished based on a logic input trigger vs a hz value threshold.