How to wire 3P NSX with micrologic NSX 5E/6E for single phase connection?

For 3P breaker used in single phase load with micrologic NSX 5E/6E, we recommend connecting the "Network Neutral line" on upstream pole 1 and the "Network Phase line" on upstream pole 3. (see picture below)

The micrologic ENVT voltage tap must be wired to upstream pole1 and declared with Ecoreach. The downstream pole 2 must be connected to the downstream pole 1 as well to read correct values on pole 2.

3 pole nsx connection in single phase

Schneider Electric India

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:

Need help?

Need help?

Product Selector

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Get a Quote

Start your sales enquiry online and an expert will connect with you.

Where to buy?

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Centre

Help Centre

Find support resources for all your needs, in one place.

  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Centre
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Contact support - +1800-103-0011
  • Price List
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings