Why are my measurement incorrect?
Incorrect readings usually happen when the phase wires (R, Y, B) and the current transformers (C1, C2, C3) are not connected to their matching phases.
The ENMOD3P expects each CT to be aligned with its corresponding phases. If the connections are mismatched or reversed, the device cannot measure accurately. To avoid this, always follow the wiring diagram and instructions provided in the user manual to ensure correct phase-to-CT alignment.