Can the CAFI breakers be used in NQOD panelboards?
Issue:
Verify CAFI, combination Arc Fault breakers can be used in the obsolete NQOD panelboards
Product Line:
Obsolete NQOD Panel
Environment:
Products sold in North America
Resolution:
Yes, both the QO or QOB CAFI breakers can be used in NQOD panelboards.
Verify CAFI, combination Arc Fault breakers can be used in the obsolete NQOD panelboards
Product Line:
Obsolete NQOD Panel
Environment:
Products sold in North America
Resolution:
Yes, both the QO or QOB CAFI breakers can be used in NQOD panelboards.