How to upgrade XBTL application with Siemens MPI driver?

Goals and Symptoms

How to upgrade XBTL application with Siemens MPI driver?

Facts and Changes

- for terminal XBTF024110 (CPU base 386): the MPI driver to select was "Siemens MPI S7", with XBTL version < V4.42
- for terminal XBTF024110(2) (CPU base Celeron, ROHS board): the MPI driver is now "MPI 3964R S7", and a gateway XBTZ979 must be added, with XBTL version > V4.42 : we recommend to use XBTL V4.51

Causes and Fixes

>>> Regarding Software:
- Use XBTL V4.51, and open the "old" application.
-Change terminal type from XBTFxx to the equivalent XBTFxx(2)
- save the application as "new"
- When upgrading an application (from "old" to "new"), you must consider those main differences about variable types:
1). Word -> Same in old and new applications
2). Double Word -> Same in old and new applications
3). Bit -> Some of them are different

Some of the bit addresses could not be converted correctly, it is due to the respective internal treatment of these two protocols in L1000.


Protocol Siemens S7 MPI MPI (3964R S7)
Bit Format Ûk Wi,j DBn DBXi.j
j 0~15 0~7

The conversion expression is:
IF J > 7 THEN
J -= 8; // Because the value of j cannot be more than 7 in MPI(3964R7) protocol.
ENDIF

>>> Regarding Hardware:
Add the following to connect XBTF to SiemensPLC:
- XBTZ 979 gateway
- XBT-Z9722 cable (provided with XBT-Z979)

슈나이더 일렉트릭 Korea

자세히 알아보기
제품군
자세히 알아보기
제품군

도움이 필요하신가요?

도움이 필요하신가요?

제품 선택기

제품 선택기

애플리케이션에 적합한 제품과 액세서리를 빠르고 쉽게 찾을 수 있습니다.

견적 받기

견적 받기

영업 관련하여 온라인으로 문의하시면 전문가가 연락드립니다.

구매처

구매처

해당 지역의 가장 가까운 슈나이더 일렉트릭 대리점을 쉽게 찾을 수 있습니다.

지원 센터

지원 센터

한 곳에서 모든 요구 사항에 대한 지원 리소스를 찾아보십시오.

  • 제품 문서
  • 소프트웨어 다운로드
  • 제품 선택기
  • 제품 대체 및 교체
  • 지원 및 연락처 센터
  • 영업소 검색
  • 견적 받기
  • 슈나이더 일렉트릭 커뮤니티
  • 채용
  • 회사 소개
  • 부정 행위 보고
  • 접근성
  • 뉴스룸
  • 투자자
  • Ecostruxure
  • 작업 검색
  • 블로그
  • 개인정보 취급방침
  • 쿠키 공지
  • 사용 약관
  • Change your cookie settings