{}

브랜드

Impact-Company-Logo-English Black-01-177x54

슈나이더 일렉트릭 코리아 웹사이트에 방문해 주셔서 감사합니다.

슈나이더 일렉트릭 코리아 웹사이트 방문자 분들 모두 환영합니다.
FAQ 검색
PME 7.2 Installation Configure Object Factory Tools Failed

Issue
PME 7.2 Installation will fail at Configure Object Factory Tools: Couldn't Run Exe.

The error appears as follows:

Product Line
PME 7.2

Environment
Inplace upgrade installation with custom reports

Cause
Custom assembly files located in the ReportDataService/bin folder cause the ObjectFactoryConfig.exe tool to fail loading all the dependencies for the assembly file.

Resolution
Please take a look at the log by clicking the open log button on the installer. It references a dll file in the ReportDataService/bin folder. In the screen shot above, the dll file is called Reporting.LogicalMeasurementExtension.Web.dll
Please remove that file from the ReportDataService/bin folder and run the installer again. It will pass the "Configure Object Factory Tools" step.
Note: There may be multiple files to be removed from ReportDataService/bin depending on the number of custom assemblies that exist.

슈나이더 일렉트릭 Korea