브랜드

슈나이더 일렉트릭 코리아 웹사이트에 방문해 주셔서 감사합니다.

슈나이더 일렉트릭 코리아 웹사이트 방문자 분들 모두 환영합니다.
		
오늘 무엇을 도와드릴까요?
Explanation of Voltage and Current Input Wiring Diagram for ION8650/8600 Form 35 and 35S, 4-Wire WYE, 2 PTs, 3 CTs

Issue
When the ION8650 is set to 35 or 35S, 4-Wire WYE, 2 PTs, 3 CTs, the meter does not seem to read correctly.

Product Line
ION8650
ION8600

Environment
System Setup

Resolution
***This configuration can affect some of the meters parameter calculations. Contact Schneider Electric for details.***
This configuration will work for measuring total power. When an ION8650/8600 series meter is applied in this way, some of the many parameters that are provided appear to be calculated incorrectly because of the way the Volts Mode works.

Please note: The following setup does not work for unbalanced systems.

1

  1. Phase to Neutral Voltages

Will not be displayed, because DELTA mode does not display line-to-neutral voltages.

  1. Phase to Phase Voltages

Vab and Vbc will display phase to neutral voltages. Vca will correctly show the phase-to-phase voltage. Vll avg will be incorrect.

  1. Current

Since the CT secondary windings are delta connected, the displayed Ib value is ?(3) * ?(3) or 3 times larger than Ia and Ic. Where Ia = ?(3)I1 AND Ic = ?(3)I3 and the I1 and I3 are currents in the primary.

  1. Real Power

The kW total will be correct.

  1. Reactive Power

The kVAr total will be correct.

  1. Apparent Power

The kVA total will be correct.

  1. Power Factor

The PF total will be correct.


Summary for Delta Mode:

ValidNot Valid
VcaVab, Vbc,- Incorrectly shows Vln values
kW totVll avg - Incorrect
kVAr totIa, Ib, Ic - Incorrect
kVA tottext
pf tottext

슈나이더 일렉트릭 Korea

자세히 알아보기
제품군
자세히 알아보기
제품군
  • 제품 문서
  • 소프트웨어 다운로드
  • 제품 선택기
  • 제품 대체 및 교체
  • 지원 및 연락처 센터
  • 영업소 검색
  • 견적 받기
  • 슈나이더 일렉트릭 커뮤니티
  • 채용
  • 회사 소개
  • 부정 행위 보고
  • 접근성
  • 뉴스룸
  • 투자자
  • Ecostruxure
  • 작업 검색
  • 블로그
  • 개인정보 취급방침
  • 쿠키 공지
  • 사용 약관
  • Change your cookie settings