PowerLogic SCADA Web Client Returns #COM and 'No Protection Key is Found' When the Loopback IP is Used in Network Addresses

Issue

PowerLogic SCADA (PLS) Web Client returns #COM for all values and displays the popup message: “No Protection Key is Found.” Runtime on the server machine functions normally (no #COM).

Product Line

Power SCADA Operations 8.2

Power Operation 2020 and 9.0

Power Operation 2021

Power Operation 2022

Power Operation 2023

Power Operation 2024

Environment

PowerLogic SCADA (PLS) – Web Client

Cause
The Loopback IP Address (127.0.0.1) is used in Network Addresses within the primary project and/or any Included Projects.
When loopback is used, remote clients look to themselves for data and for licensing, resulting in #COM values and the “No Protection Key is Found” popup.

Resolution

  1. In Citect Explorer, highlight the project.
  2. Open Citect Project Editor → Servers → Network Addresses.

Image

  1. Replace any 127.0.0.1 entries with the actual IP address assigned to the network interface used to connect to system devices.
  2. Repeat steps 2–3 for all Included Projects (Project Editor → System → Included Projects).
  3. Compile and run the project. Then relaunch the Web Client.

Note
While the Loopback Address is convenient for testing, it is highly recommended to use the actual assigned IP addresses for Network Addresses in live conditions so remote clients can resolve the correct server for data and licensing.

Recommendation:

If you are using an older version of

Power Operation, consider upgrading to the latest version for improved protocol support and security. For assistance with integration or upgrades, contact Schneider Electric Technical Support at: pmo-psup@se.com

Upgrade support

슈나이더 일렉트릭 Korea

자세히 알아보기
제품군
자세히 알아보기
제품군
  • 제품 문서
  • 소프트웨어 다운로드
  • 제품 선택기
  • 제품 대체 및 교체
  • 지원 및 연락처 센터
  • 영업소 검색
  • 견적 받기
  • 슈나이더 일렉트릭 커뮤니티
  • 채용
  • 회사 소개
  • 부정 행위 보고
  • 접근성
  • 뉴스룸
  • 투자자
  • Ecostruxure
  • 작업 검색
  • 블로그
  • 개인정보 취급방침
  • 쿠키 공지
  • 사용 약관
  • Change your cookie settings