7500 and 7600 Communication Port protection against Lightning strikes

Issue

Protection of communication ports against lightning strikes.

Product Line

PowerLogic™ Series 7500 and 7600 meters.

Environment

Industrial and commercial installations where meters are exposed to electrical disturbances, including nearby lightning strikes.

Resolution

The communication ports on the 7500 and 7600 meters (RS-232, RS-485, Ethernet, and MODEM) have been tested for resistance to nearby lightning strikes. These tests confirm compliance with IEC 61000-6-2 standards under a "Class 2 Fast" 1.2/50-microsecond Combination Wave, with a test level of ±1 kV.


Summary

Specification

All communication ports on the 7500 and 7600 meters are protected against nearby lightning strikes. Testing was conducted to meet or exceed IEC 61000-6-2 standards using a "Class 2 Fast" 1.2/50 µs Combination Wave at ±1 kV.

More Information

The surge waveform is capacitively coupled to the signal lines using a metallic capacitive clamp, simulating a conduit that typically surrounds communication cables. This method replicates the effects of a nearby lightning strike impacting the cabling conduit. Compliance with IEC 61000-6-2 is essential for CE marking and ensures robust electromagnetic compatibility in demanding environments.

슈나이더 일렉트릭 Korea

자세히 알아보기
제품군
자세히 알아보기
제품군
  • 제품 문서
  • 소프트웨어 다운로드
  • 제품 선택기
  • 제품 대체 및 교체
  • 지원 및 연락처 센터
  • 영업소 검색
  • 견적 받기
  • 슈나이더 일렉트릭 커뮤니티
  • 채용
  • 회사 소개
  • 부정 행위 보고
  • 접근성
  • 뉴스룸
  • 투자자
  • Ecostruxure
  • 작업 검색
  • 블로그
  • 개인정보 취급방침
  • 쿠키 공지
  • 사용 약관
  • Change your cookie settings