브랜드

슈나이더 일렉트릭 코리아 웹사이트에 방문해 주셔서 감사합니다.

슈나이더 일렉트릭 코리아 웹사이트 방문자 분들 모두 환영합니다.
		
오늘 무엇을 도와드릴까요?
How to wire Current Transformers (CT) on Sepam Series 80 relay for differential protection (ANSI 87)

Issue
Need to know how to wire CTs for differential protection (ANSI 87) on the Sepam Series 80 relay and what type of current values it generates.

Enviroment
Sepam 80 Series

Resolution

Wiring Current CTs for Differential Protection (ANSI 87)

Feeder

Feeder Feeder2

For feeder applications:

    • CTs located on primary side of transformer or motor are wired to B1 using a CCA634 connector and produce a Ia, Ib & Ic current.
    • CTs located on secondary side of transformer or motor are wired to B2 using a CCA634 connector and produce a I'a, I'b & I'c current.
Main

MainMain2

For Main applications:

    • CTs located on primary side of transformer or generator are wired to B2 using a CCA634 connector and produce a I'a, I'b & I'c current.
    • CTs located on secondary side of transformer or generator are wired to B1 using a CCA634 connector and produce a Ia, Ib & Ic current.

슈나이더 일렉트릭 Korea

자세히 알아보기
제품군
자세히 알아보기
제품군
  • 제품 문서
  • 소프트웨어 다운로드
  • 제품 선택기
  • 제품 대체 및 교체
  • 지원 및 연락처 센터
  • 영업소 검색
  • 견적 받기
  • 슈나이더 일렉트릭 커뮤니티
  • 채용
  • 회사 소개
  • 부정 행위 보고
  • 접근성
  • 뉴스룸
  • 투자자
  • Ecostruxure
  • 작업 검색
  • 블로그
  • 개인정보 취급방침
  • 쿠키 공지
  • 사용 약관
  • Change your cookie settings