What causes Unity error "Due to alignment constraint, you have to decrease or increase topological address index of 1"?
In Unity Pro/Control Expert, 32 bit datatypes must be mapped to an even address boundary when using the M340 & M580 PLCs.
For example, variables of REAL or DINT datatypes must be mapped to %MW2, not %MW1.
If this FAQ did not solve your issue, you can chat with us at chat with us or e-mail us at customer.services@se.com to create a case with our Technical Support Team.
If you are not located in North America, please contact your local Customer Care Center for assistance:
게시 대상: 슈나이더 일렉트릭 Korea



