How are preset speeds set up on the ATV312 drive?

Issue:
Preset speeds on the ATV312 drive.

Product Line:
Altivar 312

Environment
:All

Cause:
Preset speeds

Resolution:
Preset speeds can be assigned by the Logic Inputs, or via Communication networks.  Program the drive for Preset Speeds using SoMove or by navigating the display built into the drive.  The programming manual section on Preset Speeds is attached for reference.

Logic inputs
RdY-- > Fun- > PSS- > PS2 = LIx.  Change the value of PS2 to the Logic input you want to use to trigger the Preset Speed.  Here “x” refers to the available logic inputs number. When this particular “LIx” is ON, the drive will run to SP2 speed value (preset speed 2).  For example, if you assign PS2 = LI3, when LI3 input is closed the drive will go to Preset Speed 2 (SP2 value entered).

Similarly, PS4, PS8 and PS16 can also be assigned to other Logic inputs to activate 4, 8 or 16 preset speeds operation respectively.  Preset speeds, SP2 – SP16 can be found under “Fun- > PSS- ” menu using the Jog dial on the drive.   Consult the Preset speed chart in the Programming Manual for how to use the different preset values.

Communication networks
RdY--> CtL > LAC = L3
Assign any one bit from bit 11th to 15th of control word of particular communication network being used on which ATV312 is being used to preset Speeds (PS2, PS4, PS8 or PS16). Communication network could be one out of Modbus, CANOpen, DeviceNet or Profibus. When assigned bit of control word is HIGH, corresponding preset speed function (PS2, PS4, PS* or PS16) will be activated and accordingly SP2 to SP16 will come into effect.

Wiring:
The drive still needs the run command in order to execute Preset Speeds.  Closing the Preset Speed input is only providing the Reference (Speed value).  The drive also needs the Command (run forward/reverse) at the same time.  To use the Logic inputs, close the Run command on LI1 to 24V terminals.

슈나이더 일렉트릭 Korea

첨부 파일
BBV46385_03 ATV312 Preset Speed.pdf [112.96 KB]
자세히 알아보기
제품군
자세히 알아보기
제품군

도움이 필요하신가요?

도움이 필요하신가요?

제품 선택기

제품 선택기

애플리케이션에 적합한 제품과 액세서리를 빠르고 쉽게 찾을 수 있습니다.

견적 받기

견적 받기

영업 관련하여 온라인으로 문의하시면 전문가가 연락드립니다.

구매처

구매처

해당 지역의 가장 가까운 슈나이더 일렉트릭 대리점을 쉽게 찾을 수 있습니다.

지원 센터

지원 센터

한 곳에서 모든 요구 사항에 대한 지원 리소스를 찾아보십시오.

  • 제품 문서
  • 소프트웨어 다운로드
  • 제품 선택기
  • 제품 대체 및 교체
  • 지원 및 연락처 센터
  • 영업소 검색
  • 견적 받기
  • 슈나이더 일렉트릭 커뮤니티
  • 채용
  • 회사 소개
  • 부정 행위 보고
  • 접근성
  • 뉴스룸
  • 투자자
  • Ecostruxure
  • 작업 검색
  • 블로그
  • 개인정보 취급방침
  • 쿠키 공지
  • 사용 약관
  • Change your cookie settings