브랜드

슈나이더 일렉트릭 코리아 웹사이트에 방문해 주셔서 감사합니다.

슈나이더 일렉트릭 코리아 웹사이트 방문자 분들 모두 환영합니다.
		
오늘 무엇을 도와드릴까요?
CM4000 - Phase Order Label Shows "512" in Vista
Issue:
When viewing the Diagnostic Tab of a CM4000 in Vista, the Phase Order shows a value of "512.0".

Product Line:
StruxureWare Power Monitoring 7.0.x
Power Monitoring Expert 7.2.x
CM4000

Environment:
Vista Diagrams

Cause:
CM4000 meters that have their Phase Order set to CBA will incorrectly display 512.0 instead of "CBA". Meters that have the Phase Order set to ABC, correctly display ABC in Vista. This is due to an issue with the CM4000 driver that incorrectly returns the numeric value of the 9th bit from register 403227, rather than a boolean 0 or 1.

Resolution:
A simple modification to the CM4000.xml file will allow Vista to display the Phase Order for CBA meters.

1) Navigate to the \\system\translators folder and open the CM4000.xml file in Notepad.
2) Find the following section of code:
<ModbusInfo IONHandle="30724" Name="PM1 PhaseOrder" ModbusAddress="403227" RequestType="R" Format="MaskedBool" Mask="0x0200">
<Enumeration Ordinal="0" Value="ABC"/>
<Enumeration Ordinal="1" Value="CBA"/>
</ModbusInfo>

3) Change <Enumeration Ordinal="1" Value="CBA"/> to <Enumeration Ordinal="512" Value="CBA"/>
4) Save the file and close Notepad.

Meters that are set to CBA Phase Rotation should now correctly display the CBA in the Diagnostic Tab in Vista.

*Note: It may be necessary to restart the ION Site Server service, but in most cases simply saving the CM4000.xml file will allow the change to take affect.

슈나이더 일렉트릭 Korea

자세히 알아보기
제품군
자세히 알아보기
제품군
  • 제품 문서
  • 소프트웨어 다운로드
  • 제품 선택기
  • 제품 대체 및 교체
  • 지원 및 연락처 센터
  • 영업소 검색
  • 견적 받기
  • 슈나이더 일렉트릭 커뮤니티
  • 채용
  • 회사 소개
  • 부정 행위 보고
  • 접근성
  • 뉴스룸
  • 투자자
  • Ecostruxure
  • 작업 검색
  • 블로그
  • 개인정보 취급방침
  • 쿠키 공지
  • 사용 약관
  • Change your cookie settings