{}

브랜드

Impact-Company-Logo-English Black-01-177x54

슈나이더 일렉트릭 코리아 웹사이트에 방문해 주셔서 감사합니다.

슈나이더 일렉트릭 코리아 웹사이트 방문자 분들 모두 환영합니다.
FAQ 검색
Object Error in ENM
Issue
In ENM while selecting Email from the Relay Name drop down list, an object error message opened:



Product Line
Event Notification Module 7 (ENM)

Environment
Web Browser
Internet Explorer
Windows Server 2008 R2

Cause
Windows updates were applied and IE8 (Internet Explorer 8)  was upgraded to IE11.
ENM 7 only supports IE8 in compatibility mode.

Resolution
Internet Explorer 11 was uninstalled and the browser went to the default IE8.  This resolved the problem.

슈나이더 일렉트릭 Korea