오늘 무엇을 도와드릴까요?

How do you set up the underload detection function on the ATV212 drive?

Issue:
Configuring the underload detection function on the ATV212 drive.

Product Line:
Altivar ATV21 and ATV212

Environment:
All

Cause:
Need to detect a belt breakage requires monitoring underload threshold.

Resolution:
Basic Programming:
Go to F------- and press enter, then select:
F610= set to 0 for Relay alarm
set to 1 for underload fault
F611= underload level in factory default A or amps.  If you change F701 to 0 you can set this as a % of the Drives IN current ratings.
F609= underload bandwidth
F612= underload detect time

Function works as follows
If the motor current drops below the programmed F611 amp value for the duration of the programmed F612 detection time.  The drive will trip on underload fault or alarm depending on F610 setting.


Underload Detection

슈나이더 일렉트릭 Korea

자세히 알아보기

제품군

자세히 알아보기

제품군

도움이 필요하신가요?

제품 선택기

애플리케이션에 적합한 제품과 액세서리를 빠르고 쉽게 찾을 수 있습니다.

견적 받기

영업 관련하여 온라인으로 문의하시면 전문가가 연락드립니다.

구매처

해당 지역의 가장 가까운 슈나이더 일렉트릭 대리점을 쉽게 찾을 수 있습니다.

지원 센터

한 곳에서 모든 요구 사항에 대한 지원 리소스를 찾아보십시오.