How to Change the Option Module Communication Issue Reset Behavior in the PM8000/ION7400/ION9000 series?

Issue
How to change the default behavior of the PM8000/ION7400/ION9000 options module bus to not automatically reset on an error.

Product
PM8000 series
ION7400 series
ION9000 series

Environment
ION Setup

Resolution
The default behavior is to reset the bus automatically on an error. The steps below can be used to change this behavior.

NOTE: Changing this behavior will require a user to manually reset the bus when a communication error occurs.

The reset can be performed via the front panel, web pages or by pulsing the option module reset the external Boolean module.
  1. Connect to the meter using ION Setup. *
  2. Set the meter to advanced configuration mode. *
  3. Open the Factory Module folder and open the FAC1 module.
  4. Change the Opt Mod ResetBusOnError setup register from Automatic to manual.
Screenshot of the Setup register
  1. Send changes to the meter and disconnect from ION Setup.

* Refer to the ION Setup User guide for more information 7EN02-0312-00


슈나이더 일렉트릭 Korea

자세히 알아보기
제품군
자세히 알아보기
제품군

도움이 필요하신가요?

도움이 필요하신가요?

제품 선택기

제품 선택기

애플리케이션에 적합한 제품과 액세서리를 빠르고 쉽게 찾을 수 있습니다.

견적 받기

견적 받기

영업 관련하여 온라인으로 문의하시면 전문가가 연락드립니다.

구매처

구매처

해당 지역의 가장 가까운 슈나이더 일렉트릭 대리점을 쉽게 찾을 수 있습니다.

지원 센터

지원 센터

한 곳에서 모든 요구 사항에 대한 지원 리소스를 찾아보십시오.

  • 제품 문서
  • 소프트웨어 다운로드
  • 제품 선택기
  • 제품 대체 및 교체
  • 지원 및 연락처 센터
  • 영업소 검색
  • 견적 받기
  • 슈나이더 일렉트릭 커뮤니티
  • 채용
  • 회사 소개
  • 부정 행위 보고
  • 접근성
  • 뉴스룸
  • 투자자
  • Ecostruxure
  • 작업 검색
  • 블로그
  • 개인정보 취급방침
  • 쿠키 공지
  • 사용 약관
  • Change your cookie settings