Video: How is the automatic restart function enabled on Altivar Process drives?
Resolution:
To activate this feature, follow these steps on the drive:
-
Set the control mode
- Go to: Complete Settings → Command and Reference
- Set 2 wire type to Level Control
-
Enable automatic restart
- Go to: Complete Settings → Error/Warning Handling
- Set Auto Fault Reset to Yes
-
Retry duration
- The drive will attempt to reset the fault during the time defined in Fault Reset Time
- Default value: 5 minutes
For automatic restart to work properly, all of the following must be met:
- The drive must be configured in 2-wire control mode
- A run command (RUN) must be active
- The fault must be resettable automatically
- The cause of the fault must be resolved
Note: This function does not work if the drive is controlled via the HMI or serial communication.
Enable Catch on the Fly (under Error/Warning Handling) so the drive can synchronize with the motor if it is already spinning when the restart occurs.
The lists of fault codes that can be cleared automatically are listed in the ATV600 Programming Manual and ATV900 Programming Manual.
Si este artículo no responde a tu pregunta, consulta nuestra base de datos de preguntas frecuentes, donde encontrarás respuestas a las preguntas más comunes:
Preguntas Frecuentes - Schneider Electric (se.com)
Si la sección de preguntas frecuentes no resolvió tu problema, puedes llamarnos al 55 5804 5000 Opción 1, Opción 2 o enviarnos un correo electrónico a customercare.mx@se.com para crear un caso con nuestro equipo de Soporte Técnico.
Si no te encuentras en México o Centroamérica, por favor contacta a tu Centro de Atención al Cliente local para recibir asistencia:
Support | Schneider Electric Global (se.com)
게시 대상: 슈나이더 일렉트릭 Korea
도움이 필요하신가요?
제품 선택기
애플리케이션에 적합한 제품과 액세서리를 빠르고 쉽게 찾을 수 있습니다.
견적 받기
영업 관련하여 온라인으로 문의하시면 전문가가 연락드립니다.
구매처
해당 지역의 가장 가까운 슈나이더 일렉트릭 대리점을 쉽게 찾을 수 있습니다.
지원 센터
한 곳에서 모든 요구 사항에 대한 지원 리소스를 찾아보십시오.