{}

브랜드

Impact-Company-Logo-English Black-01-177x54

슈나이더 일렉트릭 코리아 웹사이트에 방문해 주셔서 감사합니다.

슈나이더 일렉트릭 코리아 웹사이트 방문자 분들 모두 환영합니다.

FAQ 검색

When do the heatsink fans run on the ATV61 / ATV71 series drives?

Issue:
When do the heatsink fans run on the ATV61 / ATV71 series drives?

Product Line:
Altivar 61 and Altivar 71 series drives

Environment:
All models, All serial numbers.

Cause:
Information not available in current literature.

Resolution:
Heat sink fan operation differs depending on the frame size of the drive:
- for size 2 to 5B drives, fans start when the drive thermal state reaches a temperature level --> THD parameter = 70%.  The fans turns off when drive thermal is less than 60%
- for size 6 to 8 drives and 690V range drives, the fans run when the run command is given or when the drive thermal is greater than or equal to 70% and turns off when the drive thermal is less than 60% and runs for 1 minute after the run command is removed.
- for size 9 to 15 drives and 690V range drives, the fans run when the run command is given or when the drive thermal is greater than or equal to 70% and turns off when the drive thermal is less than 60% and runs for 10 minutes after the run command is removed.

For example, an ATV61HD18M3X drive (size 6), the heatsink fan starts when a Run command is given.

d
Here is a table indicating what drives are included for each Frame size:
s
NOTE that the frame sizes listed are the global engineering frame sizes.  Some documents from the US may have slightly different labels.

슈나이더 일렉트릭 Korea

자세히 알아보기
제품군
Altivar 61
자세히 알아보기
제품군
Altivar 61