오늘 무엇을 도와드릴까요?

Cannot download to new or replacement HMIGTO. "Incompatible version of Runtime" error appears

Article available in these languages:

  • 스페인어

Issue:
Unable to download to a HMIGTO HMI. Error is "Incompatible version of Runtime".

Product Line:
HMI, Magelis

Cause:
You may have a HMI unit that is no longer supported by your version of Vijeo Designer.  This occurred when Schneider Electric increased the DRAM memory of the HMIGTO to support Vijeo XD.  The chips were upgraded to 256 MB (128 MB usable for Vijeo Designer).

Resolution:
Check the date of manufacturing sticker on the HMI unit.  If it starts with 16 or greater, then this is the newer design with increased memory.
Check your version of Vijeo Designer.  It needs to be version V6.2 SP4.1 or higher.
If you have an older version of Vijeo Designer you must update it.
Schneider Electric's software download center can be accessed at https://www.se.com/us/en/download/

NOTE: If your issue persists, please reach out to us at Technical Support:
https://www.se.com/us/en/work/support/customer-care/brand-selection/

슈나이더 일렉트릭 Korea

자세히 알아보기
제품군
자세히 알아보기
제품군
  • 제품 문서
  • 소프트웨어 다운로드
  • 제품 선택기
  • 제품 대체 및 교체
  • 지원 및 연락처 센터
  • 영업소 검색
  • 견적 받기
  • 슈나이더 일렉트릭 커뮤니티
  • 채용
  • 회사 소개
  • 부정 행위 보고
  • 접근성
  • 뉴스룸
  • 투자자
  • Ecostruxure
  • 작업 검색
  • 블로그
  • 개인정보 취급방침
  • 쿠키 공지
  • 사용 약관
  • Change your cookie settings