The PQDIF file extracted from an ION8650C is empty

Issue
The CBEMA log and the power quality report for the ION8650 indicate that a PQ event but the PQDIF extractor in PME creates an empty file for the specific time range.

Product line

Power Monitoring Expert 7.2

Power Monitoring Expert 8.x

Power Monitoring Expert 9.x

Power Monitoring Expert 2021

Power Monitoring Expert 2022

Power Monitoring Expert 2023

Power Monitoring Expert 2024



Environment
PQDIF extractor

Cause
The ION8650's Sag/swell module doesn't have following outputs and therefore they are not logged in the database.
1- SubV1Avg, SubV2Avg, SubV3Avg
2- DistV1Avg, DistV2Avg, DistV3Avg
The PQDIFF extractor default templates for the ION8650 meters requires a disturbance average quantity in order to generate a PQDIFF file.

Resolution
The ION8650C, unlike the ION8650A and ION8650B, was not designed to be a power quality meter and has limited PQ capabilities. The meter by default records the min and max duration and the PQDIFF extractor can be modified  to export PQDIFF files from the ION8650C:

To Add a new custom template to PQDIFF that can export either the min or max disturbance values:

  1. Download the attached SagSwell_Voltage_Disturbance_max_values.pqt and SagSwell_Voltage_Disturbance_min_values.pqt files
  2. Copy both files to the PME_Directory\Schneider Electric\Power Monitoring Expert\config\exporters\PQDIF\templates folder
  3. Restart the ION PQDIF Exporter Service and relaunch PQDIF exporter.
  4. Select the new ION8650C templates and then run an export job in PQDIF exporter

The extracted files will contain either the mix or the min values.

슈나이더 일렉트릭 Korea

첨부 파일
SagSwell_Voltage_Disturbance_min_values.pqt [10.32 KB]
SagSwell_Voltage_Disturbance_max_values.pqt [10.32 KB]
자세히 알아보기
제품군
자세히 알아보기
제품군
  • 제품 문서
  • 소프트웨어 다운로드
  • 제품 선택기
  • 제품 대체 및 교체
  • 지원 및 연락처 센터
  • 영업소 검색
  • 견적 받기
  • 슈나이더 일렉트릭 커뮤니티
  • 채용
  • 회사 소개
  • 부정 행위 보고
  • 접근성
  • 뉴스룸
  • 투자자
  • Ecostruxure
  • 작업 검색
  • 블로그
  • 개인정보 취급방침
  • 쿠키 공지
  • 사용 약관
  • Change your cookie settings