Unity Pro V11.1 How to solve problem with DTM which cause DTM catalog update failure or DTM failure
Issue
Some "old generation" DTM, cannot be executed in Unity Pro V11.1
Product Line
Unity 11.1
Environment
Windows 10, Windows 7
Resolution
Some "old generation" DTM, cannot be executed in Unity Pro V11.1
Symptoms may be :
DTMs (non exhaustive list) :
Unity Pro V11.1 is compiled with Visual Studio 2012 and enables by default
Microsoft© Windows protection called DEP (stands for Data Execution Prevention).
DEP ensure a better protection against malicious codes attacks.
Previous versions of Unity Pro were compiled with Visual Studio 2008 that does not support DEP.
Here is a short explanation of DEP:
"The primary benefit of DEP is to help prevent code execution from data pages. Typically, code is not executed from the default heap and the stack. Hardware-enforced DEP detects code that is running from these locations and raises an exception when execution occurs. Software-enforced DEP can help prevent malicious code from taking advantage of exception-handling mechanisms in Windows"
Some “old generation” DTMs generated years ago, seems not compatible with DEP : when Unity Pro load it, Windows detects a risk in regards to DEP and throw an error.
Solution
Old generations DTM should be updated by manufacturer to comply with Microsoft DEP protection.
Alternative solution
DEP protection can be disabled on Windows 7 and 10 Operating Systems.
Procedure :
In Windows 7 and Windows 10, type cmd , then Right click on search results ‘cmd.exe’ and click on Run as Administrator.
Then, copy paste the following and hit Enter:
bcdedit.exe /set {CURRENT.EN_US} nx AlwaysOff
Reboot

To enable back DEP, type the following in command prompt and hit Enter:
bcdedit.exe /set {CURRENT.EN_US} nx AlwaysOn

This will enable back Data Execution Prevention.
Important notice
Disabling DEP may expose computer system to vulnerability and remote-code execution. So in case DEP is disabled, computer must be secured thanks to : connection to secured network, firewall protection…. etc.
Some "old generation" DTM, cannot be executed in Unity Pro V11.1
Product Line
Unity 11.1
Environment
Windows 10, Windows 7
Resolution
Some "old generation" DTM, cannot be executed in Unity Pro V11.1
Symptoms may be :
- update catalog fails
- or DTM cannot be open
DTMs (non exhaustive list) :
- Endress & Hauser Promag 100
- Rosemount 8712E Magnetic Flowmeter Rev 3
- Rosemount_644_Temperature_Transmitter_8_HART_000026_0018_8_DD1_4_181_4_DTM
- Rosemount_2051_Pressure_Transmitter_10_HART_000026_2655_A_DD1_4_173_3_DTM
- Rosemount_8712E_3_HART_000026_0057_3_DD1_4_173_2_DTM
- ....
Unity Pro V11.1 is compiled with Visual Studio 2012 and enables by default
Microsoft© Windows protection called DEP (stands for Data Execution Prevention).
DEP ensure a better protection against malicious codes attacks.
Previous versions of Unity Pro were compiled with Visual Studio 2008 that does not support DEP.
Here is a short explanation of DEP:
"The primary benefit of DEP is to help prevent code execution from data pages. Typically, code is not executed from the default heap and the stack. Hardware-enforced DEP detects code that is running from these locations and raises an exception when execution occurs. Software-enforced DEP can help prevent malicious code from taking advantage of exception-handling mechanisms in Windows"
Some “old generation” DTMs generated years ago, seems not compatible with DEP : when Unity Pro load it, Windows detects a risk in regards to DEP and throw an error.
Solution
Old generations DTM should be updated by manufacturer to comply with Microsoft DEP protection.
Alternative solution
DEP protection can be disabled on Windows 7 and 10 Operating Systems.
Procedure :
In Windows 7 and Windows 10, type cmd , then Right click on search results ‘cmd.exe’ and click on Run as Administrator.
Then, copy paste the following and hit Enter:
bcdedit.exe /set {CURRENT.EN_US} nx AlwaysOff
Reboot
To enable back DEP, type the following in command prompt and hit Enter:
bcdedit.exe /set {CURRENT.EN_US} nx AlwaysOn
This will enable back Data Execution Prevention.
Important notice
Disabling DEP may expose computer system to vulnerability and remote-code execution. So in case DEP is disabled, computer must be secured thanks to : connection to secured network, firewall protection…. etc.
게시 대상: 슈나이더 일렉트릭 Korea


도움이 필요하신가요?
제품 선택기
애플리케이션에 적합한 제품과 액세서리를 빠르고 쉽게 찾을 수 있습니다.
견적 받기
영업 관련하여 온라인으로 문의하시면 전문가가 연락드립니다.
구매처
해당 지역의 가장 가까운 슈나이더 일렉트릭 대리점을 쉽게 찾을 수 있습니다.
지원 센터
한 곳에서 모든 요구 사항에 대한 지원 리소스를 찾아보십시오.