Issue:
Customer is looking at the RPM value in the monitor menu and it does not match the actual RPM
Product line:
Altivar 212, ATV212, S-Flex
Environment:
all
Cause:
Parameter F856
Resolution:
The default setting for parameter F856 is 2 (4 pole motor). You may need to change the number of motor poles to see the correct RPM value returned on the display.
F856 can be set to:
1 - 2 poles
2 - 4 poles (default)
3 - 6 poles
4 - 8 poles
5 - 10 poles
6 - 12 poles
7 - 14 poles
8 - 16 poles
Note that the displayed value is based on nominal RPM and output frequency. It does not take motor slippage into account. The VFD does not monitor the actual motor RPM.
Customer is looking at the RPM value in the monitor menu and it does not match the actual RPM
Product line:
Altivar 212, ATV212, S-Flex
Environment:
all
Cause:
Parameter F856
Resolution:
The default setting for parameter F856 is 2 (4 pole motor). You may need to change the number of motor poles to see the correct RPM value returned on the display.
F856 can be set to:
1 - 2 poles
2 - 4 poles (default)
3 - 6 poles
4 - 8 poles
5 - 10 poles
6 - 12 poles
7 - 14 poles
8 - 16 poles
Note that the displayed value is based on nominal RPM and output frequency. It does not take motor slippage into account. The VFD does not monitor the actual motor RPM.
게시 대상:슈나이더 일렉트릭 Korea

