Issue:
ATV212 Remote Keypad switches to Frequency even though Custom RPM display has been set up
Product Line:
ATV212
Environment:
All
Cause:
NA
Resolution:
This can happen if F702 =0 so need to set F702=60 for one pair of motor poles.
ATV212 Remote Keypad switches to Frequency even though Custom RPM display has been set up
Product Line:
ATV212
Environment:
All
Cause:
NA
Resolution:
This can happen if F702 =0 so need to set F702=60 for one pair of motor poles.