{}

브랜드

Impact-Company-Logo-English Black-01-177x54

슈나이더 일렉트릭 코리아 웹사이트에 방문해 주셔서 감사합니다.

슈나이더 일렉트릭 코리아 웹사이트 방문자 분들 모두 환영합니다.
오늘 무엇을 도와드릴까요?
Why is the MTZ firmware upgrade recommendation for 1.0.202 not shown in Ecoreach v2.5 if the Masterpact MTZ Micrologic module has a lower version installed?
Issue
The recommendation to do the firmware upgrade of the Masterpact MTZ Micrologic module is linked to the connection.  When connected through an Ethernet channel, Ecoreach v2.5  will show the Masterpact MTZ module firmware version.

Resolution
To check for new firmware and execute the update, a connection via USB must be done.  In Ecoreach 2.5, the Masterpact MTZ Micrologic module firmware upgrade requires a connection via the USB channel.

슈나이더 일렉트릭 Korea