Can we bypass Altivar process drive like we can bypass Altistart?

Once you bypass the Altivar you are losing its best feature - to regulate motor speed.
But I can understand the use of Altivar only for starting high-torque applications, like mills, up-hill conveyors, crushers, mixers, etc.
Well, ATV is not so easy to bypass because there is energy conversion AC-->DC-->AC. The most sensitive is the Altivar output. Therefore the bypass is possible only if you disconnect Altivar output from the motor before connecting motor to mains using a bypass element (contactor for instance). Take this sequence seriously because if Altivar output gets connected to mains, short circuit in AAltivar occurs. Therefore the best idea is to use Altivar  output contactor with additional mechanical and electrical interlock between ATAltivar V output contactor and bypass contactor. After bypass activation, Altivar  input side can remain connected to AC mains or can be disconnected, it is fully optional.
1. Connect Altivar to mains and to motor
2. Start the motor.
3. When motor achieves full speed, activate freewheel stop (to avoid output phase loss on Altivar if output contactor gets open)
4. Switch off Altivar output contactor
5. Switch on bypass contactor
6. Optionally you can switch off ATV from mains, move it to garage or sell it.

슈나이더 일렉트릭 Korea

자세히 알아보기
제품군
자세히 알아보기
제품군

도움이 필요하신가요?

  • 제품 선택기

    애플리케이션에 적합한 제품과 액세서리를 빠르고 쉽게 찾을 수 있습니다.

  • 견적 받기

    영업 관련하여 온라인으로 문의하시면 전문가가 연락드립니다.

  • 구매처

    해당 지역의 가장 가까운 슈나이더 일렉트릭 대리점을 쉽게 찾을 수 있습니다.

  • 지원 센터

    한 곳에서 모든 요구 사항에 대한 지원 리소스를 찾아보십시오.

  • 제품 문서
  • 소프트웨어 다운로드
  • 제품 선택기
  • 제품 대체 및 교체
  • 지원 및 연락처 센터
  • 영업소 검색
  • 견적 받기
  • 채용
  • 회사 소개
  • 부정 행위 보고
  • 접근성
  • 뉴스룸
  • 투자자
  • Ecostruxure
  • 작업 검색
  • 블로그
  • 개인정보 취급방침
  • 쿠키 공지
  • 사용 약관
  • Change your cookie settings