브랜드

Impact-Company-Logo-English Black-01-177x54

슈나이더 일렉트릭 코리아 웹사이트에 방문해 주셔서 감사합니다.

슈나이더 일렉트릭 코리아 웹사이트 방문자 분들 모두 환영합니다.
		
오늘 무엇을 도와드릴까요?
Could not open connection to the host, on port 23 Error when trying to telnet to an ION meter.

Article available in these languages: Czech

Issue
Unable to make the telnet connection to an ION meter, the following message is returned:
Connecting To  (ip address) XX.XXX.XXX.XXX....Could not open connection to the host, on port 23: Connect Failed.

Product Line
ION meters

Environment
Telnet connection to ION meters.

Cause
Windows Firewall may be blocking the Telnet inbound connection.

Resolutions
  1. Click the Start menu then search for and open Windows Firewall.
  2. Select Advanced Settings.
  3. Select Inbound Rules from the left hand pane
  4. Under Inbound Rule Actions. select New Rule.
  5. For the Rule Type select Port, click next, then select TCP and Specific Local Ports.
  6. Enter 23 for the port number and click next.
  7. Select Allow Connection then click next.
  8. Specify when the new rule can be applied. (Domain, Private, and Public)
  9. Give the Inbound Rule a name such as "Telnet" then click finished.

Test Telnet functionality again with an ION meter to ensure proper connectivity.

screenshot of windows firewall

슈나이더 일렉트릭 Korea

자세히 알아보기
제품군
자세히 알아보기
제품군
  • 제품 문서
  • 소프트웨어 다운로드
  • 제품 선택기
  • 제품 대체 및 교체
  • 지원 및 연락처 센터
  • 영업소 검색
  • 견적 받기
  • 슈나이더 일렉트릭 커뮤니티
  • 채용
  • 회사 소개
  • 부정 행위 보고
  • 접근성
  • 뉴스룸
  • 투자자
  • Ecostruxure
  • 작업 검색
  • 블로그
  • 개인정보 취급방침
  • 쿠키 공지
  • 사용 약관
  • Change your cookie settings