- A code appears in Event log for each control operation:
0 Command completed successfully
1 Local command blocked because switch position is intermediate or unknown
2 Local command blocked because switch position is already in correct state
3 Local command canceled by user
4 Switch position did not change within configured maximum operation time
5 Command blocked by Head Unit interlocks, e.g. motor supply fault or battery low
6 Command failed due to timeout waiting for enable from Head Unit
7 Local command blocked because disabled by configuration
8 Local command blocked because local/remote status is unknown
9 Local command blocked because local/remote status is remote
10 Local command blocked because automation is on
11 Remote command blocked because automation is on
12 Sectionalizer command blocked because automation is off
13 Sectionalizer command blocked because local/remote status is unknown
14 Sectionalizer command blocked because local/remote status is local
15 Unexpected command source (firmware error)
16 Remote command blocked because requested position is not a valid value
17 Command blocked because a command is already in progress for this module
18 Command blocked because the power shutdown signal is active
19 Command blocked because a command is already in progress for another module
20 Command blocked because measured switch position is intermediate or unknown
21 Command blocked because measured switch position is the same as the requested position
22 Command blocked because earth switch position is open
23 Open command blocked because external input is false
24 Open command blocked because external input is true
25 Close command blocked because external input is false
26 Close command blocked because external input is true
27 Commands blocked because module behaviour mode is off