SEPAM Trip Curves: Type 1 versus Type 1.2
Issue
User would like to understand the difference in tripping characteristics between Type 1 and Type 1.2 trip curves on SEPAM relays.
Product
SEPAM Series 20
SEPAM Series 40
SEPAM Series 80
Environment
SFT2841 configuration software
Cause
Confusion arises due to the availability of two curve types (Type 1 and Type 1.2) that appear similar but have different pickup conditions, which affects protection coordination and relay response.
Resolution
SEPAM relays offer two selectable trip curve types: Type 1 and Type 1.2.
- Type 1 Curve:
- Pickup occurs when the measured current equals the relay threshold setting
- Condition: I = Is
- Type 1.2 Curve:
- Pickup occurs when the measured current reaches 1.2 times the relay threshold setting
- Condition: I = 1.2 × Is
- After pickup, it follows the same tripping characteristics as the standard Type 1 (IEC) curve
Key difference:
- The only distinction between the two curves is the pickup level
- Once pickup is reached, both curves behave identically in terms of time-current characteristics
For further analysis and visualization:
- Refer to the available trip curve calculators for SEPAM and MiCOM relays
- Review the comparison charts showing Type 1 vs Type 1.2 characteristics
게시 대상: 슈나이더 일렉트릭 Korea
도움이 필요하신가요?
제품 선택기
애플리케이션에 적합한 제품과 액세서리를 빠르고 쉽게 찾을 수 있습니다.
견적 받기
영업 관련하여 온라인으로 문의하시면 전문가가 연락드립니다.
구매처
해당 지역의 가장 가까운 슈나이더 일렉트릭 대리점을 쉽게 찾을 수 있습니다.
지원 센터
한 곳에서 모든 요구 사항에 대한 지원 리소스를 찾아보십시오.