EM4800/E4800 error sending configuration to the meter from the configuration tool

Issue
When sending configuration and settings from configuration tool to EM4800/E4800 meter, an error occurs stating "Please review the reporting window times and reporting time zone. The current values are invalid. The reporting window must be smaller than 24hrs, it must be greater than or equal to zero".

Product
EM4800/E4800/EM4000 tenant meters

Environment
EM4800/E4800/EM4000 configuration tool

Cause
The Reporting Schedule "Start Time" and "End Time" are not set up correctly.

Resolution
The error in the screenshot below appears when one attempts to save the configuration. This error is due to the default start and end time in the report section.

Image showing the 'Error'

Note that, the device takes time in UTC while defining the Start Time and End Time of the reporting schedule. For example, pacific time is UTC-8, incorporate the offset in desired reporting time, save the configuration again.

Working with time

E4800/EM4800/E4000/EM4000 documentation can be found here FA212909

E4800/EM4800/E4000/EM4000 configuration utility is available in FA369955

슈나이더 일렉트릭 Korea

도움이 필요하신가요?

도움이 필요하신가요?

제품 선택기

제품 선택기

애플리케이션에 적합한 제품과 액세서리를 빠르고 쉽게 찾을 수 있습니다.

견적 받기

견적 받기

영업 관련하여 온라인으로 문의하시면 전문가가 연락드립니다.

구매처

구매처

해당 지역의 가장 가까운 슈나이더 일렉트릭 대리점을 쉽게 찾을 수 있습니다.

지원 센터

지원 센터

한 곳에서 모든 요구 사항에 대한 지원 리소스를 찾아보십시오.

  • 제품 문서
  • 소프트웨어 다운로드
  • 제품 선택기
  • 제품 대체 및 교체
  • 지원 및 연락처 센터
  • 영업소 검색
  • 견적 받기
  • 슈나이더 일렉트릭 커뮤니티
  • 채용
  • 회사 소개
  • 부정 행위 보고
  • 접근성
  • 뉴스룸
  • 투자자
  • Ecostruxure
  • 작업 검색
  • 블로그
  • 개인정보 취급방침
  • 쿠키 공지
  • 사용 약관
  • Change your cookie settings