브랜드

슈나이더 일렉트릭 코리아 웹사이트에 방문해 주셔서 감사합니다.

슈나이더 일렉트릭 코리아 웹사이트 방문자 분들 모두 환영합니다.
		
오늘 무엇을 도와드릴까요?
How long will it take to fill up Com'X on-board memory?
Issue

The customer is asking how long will it take to fill up the Com'X on-board memory?

Product Line

Com'X 210, 520

Cause
Often time customers use Com'X without Energy Operation or Facility Expert subscription or publishing to a network drive and uses Historical Trend feature from Com'X web page where Com'X draws datapoints from it's on-board memory. With regular on-board logging on for the connected devices, customers wonder by when Com'X's on-board memory will be full.

Resolution
Com'X can store data for 2 years given the following parameters: 32 devices logging 100 topics at every 10 minutes.  If the customer is logging more often than that, it is not possible to guarantee that Com'X will retain 2 years worth of data in it's on-board memory.  HOWEVER, the Com'X is designed to periodically export data.  We recommend that the Com'X is configured to take advantage of this feature.  It's best that the Com'X export data to a device with a larger data storage capacity.

슈나이더 일렉트릭 Korea

자세히 알아보기
제품군
자세히 알아보기
제품군
  • 제품 문서
  • 소프트웨어 다운로드
  • 제품 선택기
  • 제품 대체 및 교체
  • 지원 및 연락처 센터
  • 영업소 검색
  • 견적 받기
  • 슈나이더 일렉트릭 커뮤니티
  • 채용
  • 회사 소개
  • 부정 행위 보고
  • 접근성
  • 뉴스룸
  • 투자자
  • Ecostruxure
  • 작업 검색
  • 블로그
  • 개인정보 취급방침
  • 쿠키 공지
  • 사용 약관
  • Change your cookie settings