undefined undefined
{}

브랜드

Impact-Company-Logo-English Black-01-177x54

슈나이더 일렉트릭 코리아 웹사이트에 방문해 주셔서 감사합니다.

슈나이더 일렉트릭 코리아 웹사이트 방문자 분들 모두 환영합니다.
오늘 무엇을 도와드릴까요?
How to check Heat Tag and communication gateways on Smart solutions tab in NL 4.9.3 version of Ecodial .
Steps to check Heat Tag and communication gateways in Smart solution tab in Ecodial :
STEP-1 Launch Ecodial 4.9.3 NL version of Ecodial
STEP-2 Create a network with 50, 100 and 200A load.
STEP-3  Run the calculation
STEP-4  GO to Smart solution tab
STEP-5 Under fire prevention tab  select the required circuit breaker & switchboards to be protected
STEP-6 Run Smart solution by clicking “ SMART SOLUTION” TAB
STEP-7 Smart solution results will appear as below :
Under  “Electrical Fire prevention” solutions check there exists heat tags and communication gateways for the respective switchboards which is  required  for fire prevention.
STEP -8 Follow the instruction which application is suggesting in “ Electrical  Fire prevention “tab.
STEP-9  After following the instruction by adding add on RCD go to “ smart solution tab “ and again “ Run smart solution”
STEP10 – Network will charge out “ Heat  tag solution and communication gateways “ for respective circuit breakers and switchboard as below:



슈나이더 일렉트릭 Korea

자세히 알아보기
제품군
유용한 문서
자세히 알아보기
제품군