{}

브랜드

Impact-Company-Logo-English Black-01-177x54

슈나이더 일렉트릭 코리아 웹사이트에 방문해 주셔서 감사합니다.

슈나이더 일렉트릭 코리아 웹사이트 방문자 분들 모두 환영합니다.
FAQ 검색
How to disable alarm redirection from script
Below is an example showing how alarm redirection may be disabled from a mimic script. The script retrieves a list of all points in the database that contain "Script Disable Alarm Redirection" in their full names and disables alarm redirection for each point in the list.

DISCLAIMER: Please note this is an example only and should only be used in a test environment. The script should not be used on a live production system without making the necessary adjustments and testing for each application.
Sub DisableAlarmRedirection

Dim DGRS, DGRSRows, DGRSColNames, oPoint

Set DGRS = Server.Query("SELECT FULLNAME FROM CDBPoint WHERE FullName LIKE '%Script Disable Alarm Redirection%'")

If Not(DGRS.Error) Then
    DGRows = DGRS.Rows
    DGColNames = DGRS.ColumnNames
    For r = 0 To (DGRS.RowCount - 1)       
        Set oPoint = Server.FindObject(DGRows(r,0))
        oPoint.Interface.AlarmRedirection=False            
    Next
Else
    Msgbox DGRS.ErrorMessage, vbCritical + vbOKOnly, "Error in SQL Command" 
End If

End Sub

슈나이더 일렉트릭 Korea

자세히 알아보기
제품군
유용한 문서
자세히 알아보기
제품군