How to address the error code 5 of GOOSE Control Block?
Customer met with Error code 5 for GOOSE Control Block by using BMENOP0300.
How to address the issue? BMENOP0300
Last error 5 means goose time out which indicates the insufficient timeout setting(see below) in the goose configuration.
This is for publisher, the subscriber would decide its "Time Allowed to Live" based on the setting provided by publisher, and subscriber has no para to adjust this .
게시 대상: 슈나이더 일렉트릭 Korea

