Smart UPS - 'Mains input bad' Event Messages after switching 3‑Phase input Source
Issue
The UPS logs the following events:
- UPS: Main input bad. (0x01B0)
- UPS: Main input bad cleared. (0x01B1)
- UPS: Main input bad. (0x01B0)
- UPS: Main input bad cleared. (0x01B1)
- UPS: On battery power due to frequency and phase difference. (0x010)
These events typically occur when switching from a 3‑phase primary input source to a 3‑phase secondary source, such as a generator, or when switching back from the secondary source to the primary.
Both sources are accepted by the UPS when it is started on either one individually, and no issues occur when the input is changed to single‑phase.
Product Line
SRT8KRMXLI, SRT10KRMXLI
Environment
3 phase input with a secondary source
Resolution
This issue can arise when the phase order is different between the two input sources. At the start-up, the UPS will accept any phase sequence. But during the switchover, it's looking for the same sequence as previously receiving.
게시 대상: 슈나이더 일렉트릭 Korea




도움이 필요하신가요?
제품 선택기
애플리케이션에 적합한 제품과 액세서리를 빠르고 쉽게 찾을 수 있습니다.
견적 받기
영업 관련하여 온라인으로 문의하시면 전문가가 연락드립니다.
구매처
해당 지역의 가장 가까운 슈나이더 일렉트릭 대리점을 쉽게 찾을 수 있습니다.
지원 센터
한 곳에서 모든 요구 사항에 대한 지원 리소스를 찾아보십시오.