Behavior before HF installation Customers using Control Expert V15.0 SP1 who replace a Low-end M580 CPU with a High-End M580 CPU and use SFC code in their application, will encounter a PLC crash after doing a Rebuild All project and transfer the application to the PLC and go in RUN. Low End CPU list: Standalone BMEP 58 10••, 20••, 30••, 40••, Hot-standby BMEH 58 2040, 4040, Safety standalone BMEP 58 2040S,4040S. Safety hot-standby BMEH 58 2040S,4040S High-End CPU list: Standalone BMEP 58 5040, 6040 Hot- standby BMEH 58 6040 Safety standalone - Safety hot-standby BMEH 58 6040S New behavior after installation of ControlExpert_V150_HF004_SP1 After installing the Hot Fix when running EcoStruxure Control Expert V15.0 SP1, no SFC code generation errors are reported.