ATV71 how can your program the normally closed contact on the R1 relay (terminals R1B to R1C) for a run status?
Issue:
On the ATV71, trying to program the normally closed contact on the R1 relay (terminals R1C to R1B) for a run status.

Product Line:
Altivar Machines, Altivar 61, Altivar 71

Environment:
All models and serial number

Cause:
N/A

Resolution:
By default on the ATV71 drives, R2 is configured as a Drive Run contact.  To change R1 to Drive running:

Go into Main Menu > Drive Menu > 1.5 Inputs/Outputs Cfg > R1 Configuration.  Select Drive running and push Enter to save.